LiveWire Core 1300 Technical Specifications
Specification
|
Description
|
---|---|
Base
|
OEM PowerEdge R6615 Server
|
Chassis
|
2.5" Chassis with up to 10 Hot Plug Hard Drives
|
Motherboard
|
PowerEdge R6615 Motherboard
|
Processor
|
AMD 9254 2.9GHz 24C/48T (1)
|
Memory
|
32GB RDIMM, 5600MT/s, Dual Rank (4)
|
RAID/Internal Storage Controllers
|
PERC H755 SAS, Front
|
Hard Drive
|
BOSS-N1 controller card + with 2 M.2 960GB (RAID 1)
2.4TB Hard Drive SAS ISE 12Gbps 10K 512e (10)
|
Network Adapters
|
Broadcom 5720 Dual Port 1GbE LOM
Broadcom 57416 Dual Port 10GbE BASE-T Adapter, OCP NIC 3.0
|
Fans
|
Very High Performance Fan x4
|
Power Supply
|
Dual, Hot Plug, Redundant Power Supply (1+1), 1100W
|
Power Cords
|
C13 to C14, PDU Style, 12 AMP, 6.5 Feet (2m) Power Cord, North America
|
PCIe Riser
|
Riser Config 3, 2 x 16 FH
|
Embedded Systems Management
|
iDRAC9, Enterprise
|
Quick Sync
|
None
|
Rack Rails
|
ReadyRails Sliding Rails Without Cable Management Arm
|
PSU Specifications:
PSU
Class
Heat Dissipation (Maximum)
Frequency
Voltage
Current
|
1100W Mixed Mode
Titanium
4100 BTU/hr
50/60 Hz
100–240 V AC, autoranging
12 - 6.3 A
|
Temperature Specifications ASHRAE A2:
|
|
Allowable continuous operations
|
|
Temperature range for altitudes <= 900 m (<= 2953 ft)
|
10 to 35°C (50 to 95°F) with no direct sunlight on the platform
|
Humidity percent range (non-condensing at all times)
|
8% RH with -12°C minimum dew point to 80% RH with 21°C (69.8°F) maximum dew point
|
Operational altitude de-rating
|
Maximum temperature is reduced by 1°C/300 m (1.8°F/984 Ft) above 900 m (2953 Ft)
|
Temperature Specifications ASHRAE A3:
|
|
Allowable continuous operations
|
|
Temperature range for altitudes <= 900 m (<= 2953 ft)
|
5 to 40°C (41 to 104°F) with no direct sunlight on the equipment
|
Humidity percent range (non-condensing at all times)
|
8% RH with -12°C minimum dew point to 85% RH with 24°C (75.2°F) maximum dew point
|
Operational altitude de-rating
|
Maximum temperature is reduced by 1°C/175 m (1.8°F/574 Ft) above 900 m (2953 Ft)
|
Temperature Specifications ASHRAE A4:
|
|
Allowable continuous operations
|
|
Temperature range for altitudes <= 900 m (<= 2953 ft)
|
5 to 45°C (41 to 113°F) with no direct sunlight on the equipment
|
Humidity percent range (non-condensing at all times)
|
8% RH with -12°C minimum dew point to 90% RH with 24°C (75.2°F) maximum dew point
|
Operational altitude de-rating
|
Maximum temperature is reduced by 1°C/125 m (1.8°F/410 Ft) above 900 m (2953 Ft)
|
Common Environmental Specifications:
|
|
Maximum temperature gradient (applies to both operation and non-operation)
|
20°C in an hour* (36°F in an hour) and 5°C in 15 minutes (9°F in 15 minutes), 5°C in an hour* (9°F in an hour) for tape hardware
NOTE:* - Per ASHRAE thermal guidelines for tape hardware, these are not instantaneous rates of temperature change.
|
Non-operational temperature limits
|
-40 to 65°C (-40 to 149°F)
|
Non-operational humidity limits
|
5% to 95% RH with 27°C (80.6°F) maximum dew point
|
Maximum non-operational altitude
|
12,000 meters (39,370 feet)
|
Maximum operational altitude
|
3,050 meters (10,006 feet)
|
Maximum Vibration Specifications:
|
|
Operating
|
0.21 Grms at 5 Hz to 500 Hz for 10 minutes (all operation orientations)
|
Storage
|
1.88 Grms at 10 Hz to 500 Hz for 15 minutes (all six sides tested)
|
Maximum Shock Pulse Specifications:
|
|
Operating
|
Six consecutively executed shock pulses in the positive and negative x, y, and z axis of 6 G for up to 11 ms
|
Storage
|
Six consecutively executed shock pulses in the positive and negative x, y, and z axis (one pulse on each side of the system) of 71 G for up to 2 ms
|